The interior finish of a retrofit wall cannot move, leaving 3 inches for SPF. The foam must provide at least R-20. Submitted test data give R-10.5 for 3 inches of open-cell SPF and R-21 for 3 inches of closed-cell SPF; either product has suitable vapor-control and fire-protection details. The acceptable proposal is to:
Show answer & explanation
Correct answer: D - Install 3 inches of closed-cell SPF with its approved assembly details.